BS 8491:2008(R2015)大直徑電力電纜著火完整性測試
BS 8491:2008(R2015)大直徑電力電纜著火完整性測試,BS6387一般針對直徑在20mm電纜的完整性能測試,線纜耐火測試是指發生火焰燃燒時,電線電纜產品能夠在外部火焰依然燃燒的情況下正常運行一定時間,保持線路完整性和設備正常運轉的電線電纜產品。南京睿督公司咨詢電話:025-8658 3475。
BS 8491:2008(R2015) 火災完整性測試
BS 8491:2008(R2015) Method for assessment of fire integrity of large diameter power cables for use as components for smoke and heat control systems and certain other active fire safety systems
BS 8491:2008(R2015) 用于煙和熱控制系統及特定的其他仍在繼續的火災安全系統部件的大直徑電力電纜著火完整性的評估方法
BS 8491:2008(R2015)標準適用范圍
The Standard- BS 8491:2008(R2015) describes a method for assessment of the fire integrity of large diameter power cable for use as components for smoke and heat control systems as given in BS 7346-6, and certain other active fire safety systems. It is applicable to cables of rated voltage not exceeding 600/1000V and of overall diameter greater than 20mm
電線電纜耐火最高等級為BS6387CWZ等級,BS6387-2013在火焰條件下電纜保持線路完整性的耐火試驗方法(BS6387-2013 Test method for resistance to fire of cables required to maintain circuit integrity under fire conditions)。BS6387 CWZ級別耐火測試需要通過火焰燃燒測試,水噴淋測試和機械沖擊震動燃燒測試。詳細內容請咨詢南京睿督公司咨詢電話:025-8658 3475。
英標耐火電纜標準-BS6387耐火沖擊水噴完整性測試
全球通用的耐火電纜標準的著眼點是依賴電纜絕緣保持其在火災條件下完整性的能力。英國標準BS6387“在火災條件下保持線路完整性的電纜性能要求”提出了一些衡量不同火焰溫度、噴水和機械沖擊條件下電纜性能的判據。這個被稱為“CWZ”的最高級別的標準,即耐火電纜耐火性能分類試驗標準,是目前世界上耐火電纜的最高標準。這個標準的具體試驗要求是:
英國BS6387 C類耐火電纜:經受950℃火焰燒180分鐘;
英國BS6387 W類耐火電纜:經受650℃火焰燒15分鐘和噴水澆15分鐘;
英國BS6387 Z類耐火電纜:經受950℃火焰燒和機械沖擊15分鐘。
本標準的目的為評估當電纜暴露在這些情況下,電纜是否能夠電路的完整性。這對于消防安全系統非常重要,如應急照明場所。耐火電纜國外測試標準主要有:BS8491,BS6387,BS EN 50200,BS 8491等標準。
南京睿督公司全國免費咨詢電話:400-603-6575 025-8658 3475
網址:www.fire-test.com www.fire-test.cn
郵箱:info@fire-test.com
…